Worked case: Compressor suction scrubber high-high level: trip compressor

Liquid carry-over protection for a gas compressor. Four subsystems in series: level transmitters, PLC, motor trip and suction valve. The suction valve carries most of the PFDavg: a typical picture for process SIFs.

3 min read · First Out AI knowledge library

Example drawing: Compressor suction scrubber high-high level: trip compressor
Example drawing: Compressor suction scrubber high-high level: trip compressor. Fictional unit and tags, simplified symbols.

The function

Prevents liquid entering the compressor if the scrubber level control fails. Liquid slugs can break the compressor internals and lead to a gas release at the seals or casing.

Safe state: Compressor motor stopped and suction shutdown valve closed.

Process safety time: 120 s from LAHH to liquid at the compressor inlet nozzle at maximum inflow. Required response: ≤ 40 s. Setpoint: LAHH at 75 % of the scrubber height, 2oo3.

Where the target comes from (LOPA)

Scrubber level control valve fails closed → liquid carry-over into the compressor → mechanical failure, seal or casing rupture, gas release.

ItemValueNote
Initiating event frequency0.1 per yearBPCS control loop failure (illustrative)
Probability of ignition0.3
Probability of personnel in the compressor house0.3
Operator response to high level alarm from an independent transmitter on the alarm system0.1Separate transmitter and alarm panel; 20 min available; procedure trained
Tolerable frequency1e-5 per yearCompany tolerable frequency for a single fatality (illustrative)

Mitigated event frequency without the SIF: 9.0 × 10⁻⁴ per year. Required risk reduction factor: 90. Required PFDavg: 0.011. Target: SIL 1.

Inputs (illustrative values)

GroupVotingλDU /hλDD /hλSU /hβT1PTCPartial strokeTypeSC
Level transmitters LT-1201A/B/C2oo31.5e-77e-71e-75 %1 yr90 %–BSC 3
Safety PLC1oo15e-91e-600 %10 yr99 %–BSC 3
Motor trip (two contactors in series)1oo21.5e-703e-710 %1 yr99 %–ASC 3
Suction SDV XV-12011oo15e-701e-60 %1 yr85 %–ASC 3

Mission time 20 years, low demand (PFDavg). Failure rates are illustrative values written for First Out AI, not taken from any certificate or database.

Result (First Out AI engine v0.3.0)

MeasureValue
PFDavg8.8 × 10⁻³
SIL by probability2
SIL by IEC 61511 fault tolerance2
Systematic capabilitySC 3
Achieved SIL2 (meets SIL 1)
Required PFDavg1.1e-2 (met)
Mean time to spurious trip20.3 years
GroupVotingPFDavgShareHFT / requiredSFF
Level transmitters LT-1201A/B/C2oo31.1 × 10⁻⁴1 %1 / 084 %
Safety PLC1oo12.3 × 10⁻⁴3 %1 / 0100 %
Motor trip (two contactors in series)1oo27.9 × 10⁻⁵1 %1 / 067 %
Suction SDV XV-12011oo18.4 × 10⁻³95 %0 / 067 %

Engineer's reading

  • Suction SDV XV-1201 carries 95 % of the PFDavg, so improvements there matter most.

Open this example in First Out AI: SIL verification → Examples → "Compressor suction scrubber high-high level: trip compressor".