Worked cases

Worked case: Fired heater flame failure: close fuel gas double block

Burner management trip on loss of flame. Two flame scanners and two shutdown valves in series (double block). Typical SIL 2 heater protection.

3 min read · First Out AI knowledge library

Example drawing: Fired heater flame failure: close fuel gas double block
Example drawing: Fired heater flame failure: close fuel gas double block. Fictional unit and tags, simplified symbols.

The function

Prevents accumulation of unburnt fuel gas in the firebox after a flame-out, which could ignite explosively on the hot refractory or at re-light.

Safe state: Both fuel gas shutdown valves closed, vent between them open, pilot gas isolated.

Process safety time: 4 s (flame-out to an explosive mixture at the burner, vendor data). Required response: ≤ 3 s including scanner response. Setpoint: Loss of flame on either scanner (1oo2 trip voting); scanner flame failure response time ≤ 1 s.

Where the target comes from (LOPA)

Burner flame-out with fuel gas valves open → unburnt fuel accumulates in the firebox → explosion on re-ignition.

ItemValueNote
Initiating event frequency0.1 per yearFlame instability and fuel pressure upsets, site history (illustrative)
Probability of delayed ignition producing an explosion0.5
Probability of personnel at the heater0.1
Tolerable frequency1e-5 per yearSingle fatality (illustrative)

Mitigated event frequency without the SIF: 5.0 × 10⁻³ per year. Required risk reduction factor: 500. Required PFDavg: 2.0 × 10⁻³. Target: SIL 2.

Inputs (illustrative values)

GroupVotingλDU /hλDD /hλSU /hβT1PTCPartial strokeTypeSC
Flame scanners BE-1301A/B1oo23e-71.5e-64e-710 %1 yr90 %–BSC 3
Burner management logic solver1oo15e-91e-600 %10 yr99 %–BSC 3
Fuel gas SSOVs XV-1301/13021oo26e-701e-610 %1 yr90 %–ASC 3

Mission time 20 years, low demand (PFDavg). Failure rates are illustrative values written for First Out AI, not taken from any certificate or database.

Result (First Out AI engine v0.3.0)

MeasureValue
PFDavg1.4 × 10⁻³
SIL by probability2
SIL by IEC 61511 fault tolerance3
Systematic capabilitySC 3
Achieved SIL2 (meets SIL 2)
Required PFDavg2e-3 (met)
Mean time to spurious trip12.0 years
GroupVotingPFDavgShareHFT / requiredSFF
Flame scanners BE-1301A/B1oo24.0 × 10⁻⁴27 %1 / 086 %
Burner management logic solver1oo12.3 × 10⁻⁴16 %1 / 0100 %
Fuel gas SSOVs XV-1301/13021oo28.2 × 10⁻⁴57 %1 / 063 %

Engineer's reading

  • Fuel gas SSOVs XV-1301/1302 carries 57 % of the PFDavg, so improvements there matter most.
  • With a perfect proof test (the Free plan assumption) the PFDavg would be 6.3 × 10⁻⁴; the difference to 1.4 × 10⁻³ is the effect of the realistic proof test coverage.

Open this example in First Out AI: SIL verification → Examples → "Fired heater flame failure: close fuel gas double block".