The β value for a redundant group is usually estimated with a scoring checklist. The factors are similar across methods; knowing them helps both to estimate β and to reduce it.
| Factor | Lowers β when |
|---|---|
| Separation | Channels are physically separated: separate tappings, cables, junction boxes, air supplies |
| Diversity | Channels use different technologies, manufacturers or measuring principles |
| Complexity and maturity | Devices are simple and well proven in this service |
| Analysis | Common cause failures were analysed in the design (FMEA, review) |
| Procedures and human interface | Testing and maintenance are staggered, done by different people, with procedures that check for common causes |
| Competence and training | Staff understand the common cause risks of the system |
| Environment | Temperature, humidity, vibration and contamination are controlled or the devices are rated for them |
| Diagnostics | Diagnostics detect a failure in one channel before it develops in the others |
Using the result
Most checklist methods produce a β somewhere between about 1 % (very well separated, diverse, well maintained) and 10 % or more (identical channels, shared connections). Record the score sheet with the verification; reviewers expect to see it.