Proof test coverage (PTC) is the fraction of dangerous undetected failures that a proof test actually reveals. A full-stroke test of a valve finds a stuck valve, but not necessarily a seat that leaks too much or a spring that is too weak at process conditions. Whatever the test misses stays hidden until the device is overhauled or replaced.
The arithmetic
Split λDU into two parts:
- PTC · λDU, revealed at every proof test (interval T1),
- (1 − PTC) · λDU, revealed only at renewal (interval MT, often the mission time).
PFDavg ≈ PTC·λDU·T1/2 + (1 − PTC)·λDU·MT/2
Worked example
The valve from the single-channel article: λDU = 2 × 10⁻⁶ per hour, T1 = 1 year, mission time 20 years.
| Proof test coverage | Revealed part | Hidden part | PFDavg | Band |
|---|---|---|---|---|
| 100 % | 8.8 × 10⁻³ | 0 | 8.8 × 10⁻³ | SIL 2 |
| 90 % | 7.9 × 10⁻³ | 1.8 × 10⁻² | 2.5 × 10⁻² | SIL 1 |
| 80 % | 7.0 × 10⁻³ | 3.5 × 10⁻² | 4.1 × 10⁻² | SIL 1 |
The hidden 20 % of failures accumulates for twenty years and contributes five times more than everything else. Halving T1 hardly helps; only better coverage or more frequent renewal does.
Where coverage values come from
- The device certificate or FMEDA report sometimes states the coverage of a described test.
- Otherwise the engineer estimates it by asking, failure mode by failure mode, whether the test would reveal it. Be specific about the test: a stroke test from the control room, a stroke test with timing, a test at process pressure, a seat leak test.
- Record the basis. A reviewer will ask.
Typical qualitative picture (orders of magnitude, not data): a full stroke with stroke-time check reveals most valve failure modes but not seat leakage; adding a tight shut-off test where tightness matters raises coverage further; a transmitter test that only injects a signal at the electronics does not test the sensor or the impulse line.
What to do when coverage drives the result
- Improve the test: add timing, leak tests, test at process conditions, test the solenoid separately.
- Shorten the renewal interval for the part the test misses (overhaul the valve every few years).
- Add partial stroke testing for valves, which clears part of λDU often.
- Add redundancy, accepting the common cause term.