Functional Safety · worked example, computed with First Out AI

Extending the turnaround interval: which safety functions can wait

The unit proof tests its safety functions at an annual shutdown and plans to move to two- or three-yearly turnarounds, which stretches every proof test interval. Ten functions recomputed at each interval, against the risk reduction each one was designed for, show which can follow the longer cycle.

Functions
10, SIL 1 to SIL 3
Intervals
1, 2 and 3 years
Method
SIL verification per interval
Result
6 of 10 pass at 2 years, 3 of 10 at 3 years

Question

A unit plans to extend its turnaround interval. Field devices in safety functions are proof tested at turnarounds, so their test interval grows with it. Logic solvers keep their 10-year interval and partial stroke tests continue during operation.

Each function is checked against the PFDavg its own LOPA requires, not just the upper limit of its SIL band. All ten pass today at an annual interval.

Results by function

Green: meets the required PFDavg. Red: does not.

FunctionServiceTargetRequired PFDavgPFDavg at 1 yrPFDavg at 2 yrPFDavg at 3 yrLongest interval that passes
SIF-01Separator high pressureSIL 25.00 × 10⁻³3.92 × 10⁻³6.43 × 10⁻³8.69 × 10⁻³1 yr
SIF-02Compressor high discharge temperatureSIL 10.050.02660.03310.03893 yr
SIF-03Column low level, pump protectionSIL 10.013.00 × 10⁻³4.45 × 10⁻³5.75 × 10⁻³3 yr
SIF-04Reactor high temperatureSIL 23.33 × 10⁻³2.40 × 10⁻³3.30 × 10⁻³4.17 × 10⁻³2 yr
SIF-05Heater fuel tripSIL 23.90 × 10⁻³2.34 × 10⁻³3.17 × 10⁻³4.00 × 10⁻³2 yr
SIF-06Tank high levelSIL 10.020.01740.02620.03411 yr
SIF-07HIPPS on export lineSIL 35.00 × 10⁻⁴4.58 × 10⁻⁴6.28 × 10⁻⁴7.86 × 10⁻⁴1 yr
SIF-08Fuel gas low pressureSIL 10.040.02020.02660.03233 yr
SIF-09Absorber high level to flareSIL 10.0250.01690.02360.02962 yr
SIF-10Toxic gas release isolationSIL 23.00 × 10⁻³2.14 × 10⁻³3.10 × 10⁻³4.07 × 10⁻³1 yr
The three most sensitive functions: PFDavg relative to the required value
  • SIF-06: PFDavg ÷ required
  • SIF-01: PFDavg ÷ required
  • SIF-07: PFDavg ÷ required
0.111011.522.53Proof test interval (years)PFDavg ÷ required PFDavg (log scale)Required value

Values above 1 miss the required risk reduction. Hover, tap or use the arrow keys to read each point.

Chart data
Proof test interval (years)SIF-06: PFDavg ÷ requiredSIF-01: PFDavg ÷ requiredSIF-07: PFDavg ÷ required
10.870.7840.917
21.31.31.3
31.71.71.6

Findings

At two years, four functions lose their margin: SIF-01 (separator high pressure), SIF-06 (tank high level), SIF-07 (HIPPS on export line), SIF-10 (toxic gas release isolation). At three years only three of ten still pass.

The functions that tolerate a longer interval have a large margin to begin with, usually SIL 1 functions whose LOPA asked for little more than the band minimum. The ones that fail were designed close to their requirement, and their PFDavg grows steadily with the interval.

Partial stroke testing does not save the HIPPS on its own: the tightness check and the rest of the full proof test still move with the turnaround.

Recommendations

  1. Extend the interval only for the functions that pass at the new interval, and record the recalculation in each verification report.
  2. For the others, plan online proof tests with bypass procedures, so their test interval stays at one year while the turnaround moves.
  3. Where online testing is not possible, add redundancy or improve test coverage before the interval is extended.

Worked example with an illustrative design and data, chosen to show the method; it is not a client project. Failure rates are typical of published device certificates and are not taken from any reliability database. Computed with the First Out AI engine v0.3.0 on 28.10.2026. First Out AI supports engineering judgement and does not replace it: results must be checked by a competent functional safety engineer, and First Out AI is not certified software. This is not engineering advice for a specific plant.