SIL bands and quick reference numbers

The SIL ranges for PFDavg, PFH and RRF in one table, with the hand formulas used in First Out AI articles.

2 min read · First Out AI knowledge library

SILPFDavg (low demand)RRFPFH per hour (high demand)
410⁻⁵ to below 10⁻⁴10,000 to 100,00010⁻⁹ to below 10⁻⁸
310⁻⁴ to below 10⁻³1,000 to 10,00010⁻⁸ to below 10⁻⁷
210⁻³ to below 10⁻²100 to 1,00010⁻⁷ to below 10⁻⁶
110⁻² to below 10⁻¹10 to 10010⁻⁶ to below 10⁻⁵

Hand formulas (perfect proof test, small terms omitted)

CaseApproximation
1oo1λDU · T1 / 2
1oo2((1−β)λDU·T1)² / 3 + β·λDU·T1 / 2
2oo3((1−β)λDU·T1)² + β·λDU·T1 / 2
Imperfect test, 1oo1PTC·λDU·T1/2 + (1−PTC)·λDU·MT/2
Maximum test interval, 1oo1T1 ≈ 2 · PFD_required / λDU
LOPAMEF = IEF × Π(factors); RRF = MEF / TMEL
SFF(λSD + λSU + λDD) / λtotal

Unit reminders: 8,760 hours per year; 1 FIT = 10⁻⁹ per hour.