HAZOP deviation library: atmospheric storage tanks

Typical deviations for atmospheric storage tanks, with overfill as the dominant scenario.

2 min read · First Out AI knowledge library

DeviationTypical causesTypical consequencesTypical safeguards
OverfillWrong line-up; tank gauge stuck; transfer not stopped; receipt larger than ullageLiquid spill, vapour cloud, fire or explosion, environmental damageTank gauge with high alarm; independent high-high level with automatic shut-off; ullage check before transfer; bund
OverpressureFilling faster than vent capacity; blanket gas regulator failureRoof or shell damagePressure/vacuum relief valve sized for maximum rates; emergency vent
VacuumPump-out faster than vent capacity; vent blockedTank implosionPVRV; inspection of vents
Static ignitionSplash filling of low-conductivity liquidsFire in the vapour spaceBottom entry, flow velocity limits, bonding and earthing
Leak from the bottomCorrosionSoil and groundwater contaminationInspection; leak detection; double bottom
Rim seal fire (floating roof)LightningFireRim seal fire detection and foam system

The overfill scenario has caused some of the best-known incidents in the industry; see the knowledge articles on Buncefield (2005) and the Caribbean Petroleum terminal (2009).

Written for First Out AI as engineering guidance. It supports engineering work and does not replace it; check every value against your standards, certificates and company rules with a competent functional safety engineer.