Specification and lifecycle

Application program requirements for safety PLCs

The rules that keep systematic failures out of the trip logic: language, structure, review, testing and change control.

2 min read · First Out AI knowledge library

The application program is where a correct specification can still become a wrong function. The process sector expects the program to be developed with the same discipline as the hardware.

Practices

  • Use the logic solver's limited variability language (function block diagrams, ladder) and its certified function blocks as stated in the safety manual.
  • Keep the structure simple: one function per section, inputs, voting, logic and outputs clearly separated.
  • Use naming that matches the C&E and the SRS.
  • Avoid using the safety PLC for non-safety control.
  • Review the program against the SRS and C&E by someone who did not write it.
  • Test every row of the C&E, including degraded voting, time delays, overrides and resets, in factory and site acceptance tests.
  • Version control: record the version and checksum; the proof test checks they match the approved version.
  • Change control: every change through management of change, with impact analysis and retest.

In the SRS

First Out AI has an "Application program" field written into the SRS; the proof test draft includes the program version check.